[1]丁文斌,李红英,汪昱煜,等.变压器油中溶解二氧化碳光谱监测降噪研究[J].工业仪表与自动化装置,2026,(02):104-108.[doi:10.19950/j.cnki.CN61-1121/TH.2026.02.020]
 DING Wenbin,LI Hongying,WANG Yuyu,et al.Research on noise reduction in spectral monitoring of dissolved carbon dioxide in transformer oil[J].Industrial Instrumentation & Automation,2026,(02):104-108.[doi:10.19950/j.cnki.CN61-1121/TH.2026.02.020]
点击复制

变压器油中溶解二氧化碳光谱监测降噪研究()

《工业仪表与自动化装置》[ISSN:1000-0682/CN:61-1121/TH]

卷:
期数:
2026年02期
页码:
104-108
栏目:
出版日期:
2026-04-15

文章信息/Info

Title:
Research on noise reduction in spectral monitoring of dissolved carbon dioxide in transformer oil
文章编号:
1000-0682(2026)02-0104-05
作者:
丁文斌1李红英2汪昱煜1许枢畅1
1.国能江西丰城发电有限公司,江西 丰城 331100; 2.国家能源集团科学技术研究院有限公司武汉分公司,湖北 武汉 430000
Author(s):
DING Wenbin1LI Hongying2WANG Yuyu1XU Shuchang1
1.Guoneng Fengcheng Power Generation CO., Ltd., Jiangxi Fengcheng 331100,China;2.China Energy Science and Technology Research Institute CO., Ltd., Hubei Wuhan 430000,China
关键词:
二氧化碳可调谐半导体激光吸收光谱积分梳状滤波二次谐波
Keywords:
carbon dioxide tunable diode laser absorption spectroscopy cascaded integral-comb filtering second harmonic
分类号:
O433.4
DOI:
10.19950/j.cnki.CN61-1121/TH.2026.02.020
文献标志码:
A
摘要:
为实现变压器油中溶解二氧化碳(CO2)实时监测,设计了基于可调谐半导体激光吸收光谱技术的变压器油中CO2监测装置,采用粒子群算法优化积分梳状滤波降低现场噪声对二次谐波的影响,滤波后信噪比由7.86dB提升至18.33dB,采用背景扣除技术去除怀特池吹扫过程中引入的空气中CO2成分,实现了自动取样、脱气、测量以及回油功能。在气相标定实验中,优化后的二次谐波峰谷值与浓度的拟合线性度达0.999 5,具备良好的线性关系;在油样测试中,装置的检测下限与误差满足国网A级要求,可为变压器油中溶解气体分析提供准确的CO2值。
Abstract:
In order to achieve real-time monitoring of dissolved carbon dioxide (CO2) in transformer oil, a CO2 monitoring device based on tunable diode laser absorption spectroscopy technology was designed. The device uses cascaded integral-comb filtering to reduce the impact of on-site noise on the second harmonic, and background subtraction technology to remove CO2 components introduced in the air during the blowing process of the White pool, achieving automatic sampling, degassing, measurement, and oil return functions. In the gas phase calibration experiment, the fitting linearity between the peak and valley values of the second harmonic and the concentration reached 0.9995, indicating a good linear relationship; In oil sample testing, the detection lower limit and error of the device meet the A-level requirements of the State Grid, and can provide accurate CO2 values for dissolved gas analysis in transformer oil.

参考文献/References:

[1]江浩,廖雍琦,李兴旺.一起110 kV变压器套管发热缺陷处理及油中微量乙炔分析[J].农村电气化,2023,09: 89-92.

[2]宋宏图.基于TDLAS的变压器油中溶解CO及CO2的传感研究[D].北京:华北电力大学,2017.
[3]李洋流,赵学增.基于光声光谱的变压器油中溶解气体监测系统[J].传感器与微系统,2011,30(06):103-105.
[4]蒋维,张龙飞,杨生彬,等.基于可调谐半导体激光的变压器油中CO、CO2浓度监测方法江西电力,2024, 48(02): 20-23.
[5]李秉辉.基于可调谐二极管激光吸收光谱技术的SO3气体测量参数优化[J].应用激光,2023,43(12): 133-137.
[6]程绳,陈启明,张引,等.基于中红外可调谐激光光谱技术的SO2检测[J].高压电器,2024,60(09):155-162.
[7]杨舒涵,乔顺达,林殿阳,等.基于可调谐激光吸收光谱的氧气浓度高灵敏度检测研究[J].2023,16(01): 151-157.
[8]马砺,范新丽,张朔,等.基于TDLAS技术的CH4气体检测与温度补偿方法[J].光谱学与光谱分析,2021,41(11): 3632-3638.
[9]张华乾,于庆.基于小波阈值函数降噪的实时煤矿氧气检测数据误差处理[J].煤矿机电, 2023, 44(06): 28-32.
[10]国家电网有限公司.变压器油中溶解气体在线监测装置技术规范: Q/GDW 10536-2021[S].北京: 2021.12.

相似文献/References:

[1]王航宇.西门子WinCC在二氧化碳回收系统中的应用[J].工业仪表与自动化装置,2015,(05):101.
 WANG Hangyu.Application of Siemens WinCC in the carbon dioxide recovery system[J].Industrial Instrumentation & Automation,2015,(02):101.

备注/Memo

备注/Memo:
收稿日期:2025-10-11第一作者:丁文斌(1992—),男,甘肃庆阳人,助理工程师,大学本科,主要研究方向为电气一次方面。E-mail:826733935@qq.com